Every PARTH switched extension socket is type-tested by Intertek, an accredited global laboratory, against the British Standard for 13A socket-outlets. Here are the certificates behind the product — and the real numbers from the 45-page test report.
Three independent verifications cover the full PARTH range — 2/3/4/5/6-way switched extension sockets, with or without circuit breaker, USB charger and surge protection (202X / 302X / 402X series).
Not marketing claims — measured results from report 22050477HKG-001, next to the limit the standard demands.
| Test | What was done | Measured vs limit |
|---|---|---|
| Cable flex endurance | 10,000 bend cycles at 60/min, 2 kg load, live at 14A 250V | 0 / 40 strands broken limit: ≤10% PASS |
| Dielectric strength | 3750V applied for 60s between conductors; 2000V for 1 min; 6000V on non-rewireable body | No breakdown, no flashover PASS |
| Temperature rise | Full rated load 14A 240V~ until steady state, terminals & surface probed | max 41.7K limit: ≤52K PASS |
| Glow-wire fire test | Insulating parts exposed to 650°C (750°C for parts retaining live parts) | No flame, no sustained glow PASS |
| Plug withdrawal force | Force needed to pull a compliant plug from the socket | 33–35 N limit: ≤36 N PASS |
| Earth continuity | Resistance between earth pin and every accessible metal part | ≤7.1 mΩ limit: ≤50 mΩ PASS |
| Heat ageing + ball pressure | 7 days at 70°C, then ball-pressure at 75°C on enclosures | ≤1.8 mm impression limit: ≤2 mm PASS |
| Switch endurance | Make/break at 16.25A 275V~, plus 10 slow-operate arcing cycles | No arcing damage PASS |
The report also audits every critical component. Nothing anonymous goes into a PARTH lead.
Yes. PARTH switched extension sockets are type-tested to BS 1363-2:2016 by Intertek (report 22050477HKG-001, issued May 2023, all clauses passed), and carry UKCA and CE electromagnetic-compliance verifications covering the full 202X/302X/402X range.
BS 1363-2:2016 is the British Standard for 13A switched and unswitched socket-outlets — the safety specification UK plugs and extension sockets must meet. It covers construction, temperature rise, dielectric strength, mechanical strength, glow-wire fire resistance and more.
Testing is carried out by Intertek, an accredited global testing laboratory, on samples of our switched extension sockets rated 13A 240V~.
PARTH extension leads are made in our own factory in Guangdong, China — founded in 1989, ISO 9001-certified, and exporting to over 40 countries.
Summary test data is published on this page. Verification documents are available to customers and trade partners on request — contact us and we will share them.